The white ground is going out to the pole and the green one is my grounding rod, should the green one not be bonded to the pannel not the bus bar?

Note not an electrician, but my copper water lines feel live and a few switches in my house give us shocks

you are viewing a single comment's thread
view the rest of the comments
[–] LemminNewbie@lemmy.today 5 points 3 months ago* (last edited 3 months ago) (6 children)

Not if this is the first disconnecting means after your meter. The green screw is bonding the bus bar to the panel and makes the neutral have a potential equal to that of the ground, so it is a 'return' path for the split phases to get 120V rather than the full 240V single phase that's coming from the utility. If this isn't the first panel after your meter you would isolate the neutrals from the ground/panel so you don't create parallel paths for the electricity to flow during a lightning surge. https://imgur.com/a/zVSkSug

Let me also say that messing with your own house wiring the danger is not electrocuting yourself. There's just not enough voltage to likely do that. The danger is making an improper connection that causes a fire and that's why you should get a professional if you're unsure and don't understand the risks involved.

[–] Onomatopoeia@lemmy.cafe 4 points 3 months ago* (last edited 3 months ago) (4 children)

I must disagree with the not elextrocuting yourself".

120v with 50a+ service (200 is common these days) is plenty to kill you, especially a novice.

[–] JoeBigelow@lemmy.ca 1 points 3 months ago (2 children)

What need is there for a 200 amp circuit? We had to install 50a to power a 40ft camper and it's in a separate box.

[–] LemminNewbie@lemmy.today 3 points 3 months ago (1 children)

The 200 amps would be the entire service from the utility meter for a single family home. It's definitely overkill on most houses but with the electrification of everything it's probably for future proofing. Big houses or properties with multiple detached structures will occasionally have a 400 amp service but the utility meters they put on those are only rated for 320 amps continuous so I think 400 is also overkill for those types of properties usually.

[–] CorrectAlias@piefed.blahaj.zone 1 points 3 months ago

Yeah. I have 200 amp service but it's because I have a car charger, heat pump, electric furnace, induction range, electric water heater, and a server rack. That being said, I've never even come close to using all 200 amps at once. It's at least good piece of mind in case that randomly happens for some reason, though.